Engineering · PLC · Project 1 of 15 · Motor control · Level 1

Motor start / stop (seal-in)

The most important rung in industry: press START, the motor keeps running by itself until STOP or an overload.

▶ Run it in the simulator

Virtual machine for Motor start / stop (seal-in): buttons, lamps and the process it controls
Learning model only. This page teaches the program logic. A real machine needs a proper control panel with an isolator, fuses, motor protection and a hard-wired emergency stop. Mains and motor wiring is for qualified electricians. A PLC output never drives a motor directly.

You will learn

The seal-in (latching) contact: MOTOR in parallel with START remembers that the motor is running after you let go of START. Stop buttons are wired normally closed, so the PLC input is ON when everything is healthy. A broken wire then looks like a stop press, which is the safe way to fail.

How it works

  • Press START. MOTOR turns ON and its own contact in parallel holds it.
  • Release START. The motor keeps running because MOTOR feeds itself.
  • Press STOP. The STOP contact opens, the rung loses power and MOTOR drops out.
  • Flip the Overload relay. The motor stops and will not restart until the relay is reset.

In real life

Every pump, fan, compressor and conveyor motor in a factory starts with this rung. Real panels add an emergency-stop and a motor-protection breaker in the same series chain.

Inputs, outputs and addresses

The same signals on seven PLC brands. Inputs and outputs are numbered in order; check your own hardware and software, because addresses depend on the model and module position.

NameWhat it isTypeSiemens
S7-1200
Allen-Bradley
CompactLogix
Mitsubishi
iQ-F FX5U
Delta
DVP / AS
Omron
CP2E
Schneider
M241
Inovance
H5U
STARTSTART push-button (N.O.)Input%I0.0Local:1:I.Data.0X0X00.00%IX0.0X0
STOPSTOP push-button (N.C.)Input%I0.1Local:1:I.Data.1X1X10.01%IX0.1X1
OLThermal overload contact (N.C.)Input%I0.2Local:1:I.Data.2X2X20.02%IX0.2X2
MOTORMotor contactor KM1 and RUN lampOutput%Q0.0Local:2:O.Data.0Y0Y0100.00%QX0.0Y0

Ladder diagram (shown for Siemens, live state)

Green wires carry power in the moment captured below. Switch the brand and the language in the simulator.

Rung 1 Start / stop with seal-in and overloadSTART%I0.0MOTOR%Q0.0STOP%I0.1OL%I0.2MOTOR%Q0.0

Structured text, Siemens SCL

(* Siemens S7-1200, CPU 1214C DC/DC/DC - TIA Portal - SCL *)
(* Rung 1: Start / stop with seal-in and overload *)
"MOTOR" := ("START" OR "MOTOR") AND "STOP" AND "OL";

Structured text, Allen-Bradley

(* Allen-Bradley CompactLogix 5069 (L306ER) - Studio 5000 Logix Designer - Structured Text *)
(* Rung 1: Start / stop with seal-in and overload *)
MOTOR := (START OR MOTOR) AND STOP AND OL;

Try this

Parts to buy

The links open a search on each store, so you see what is in stock today. Check the model, voltage and price before you order.

#ItemBuy / compare
1PLC with 3 inputs and 1 outputAmazon.in · IndiaMART · Robu.in
224 V DC supplyAmazon.in · IndiaMART · Robu.in
3Green N.O. and red N.C. push-buttonsAmazon.in · IndiaMART · Robu.in
4Contactor with 24 V DC coilAmazon.in · IndiaMART · Robu.in
5Thermal overload relayAmazon.in · IndiaMART · Robu.in
All projects2. Forward / reverse with interlock →

This is a learning tool. It teaches the logic, not the exact keystrokes of each vendor’s software. Check the manual of your own PLC.